A.2 Examples of acceptance tests
4.
5.
You have completed the acceptance test of the SDI function for the positive direction of rotation.
406
Test the set limit value
4.1.
Enter a negative speed setpoint.
The following test depends on how you have set the SDI function during commis‐
4.2.
sioning:
STOP A in the event of a limit value
violation
● The inverter signals the following:
C01716 and C30716
(tolerance for safe direction of
motion exceeded)
C01700 and C30700 (STOP A
initiated)
4.3.
Analyze the trace:
● When SDI+ is selected, the inverter signals: SDI+ is active (r9722.12 = 1).
● If r9713[0] > SDI tolerance, then the inverter signals an internal event
(r9722.7 = 0).
STOP A in the event of a limit value
violation
● The motor coasts down to a
standstill (r9722.0 = 1).
Acknowledge fault
5.1.
Deselect SDI+.
5.2.
Check: SDI+ is not active (r9722.12 = 0).
5.3.
Acknowledge the messages for the safety functions.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
STOP B in the event of a limit value vio‐
lation
● The inverter signals the following:
C01716 and C30716 (tolerance
for safe direction of motion
exceeded)
C01701 and C30701 (STOP B
initiated)
C01700 and C30700 (STOP A
initiated)
STOP B in the event of a limit value vio‐
lation
● The inverter brakes the motor on the
OFF3 ramp (r9722.1 = 1).
● After braking, STO is active
(r9722.0 = 1).
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD