Setting The Forced Checking Procedure (Test Stop) - Siemens Sinamics G120 Function Manual

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

5.11.3

Setting the forced checking procedure (test stop)

Requirement
You are online with STARTER or Startdrive online.
Procedure with STARTER
To set the forced checking procedure (test stop) of the basic functions, proceed as follows:
1. Select the screen form for setting the forced checking procedure.
2. Set the monitoring time to a value to match your application.
3. Using this signal, the inverter signals that a forced checking procedure (test stop) is required.
Interconnect this signal with an inverter signal of your choice.
4. Close the screen form.
You have set the forced checking procedure (test stop) for the basic functions.
Procedure with Startdrive
To set the forced checking procedure (test stop) of the basic functions, proceed as follows:
1. Select the screen form for setting the forced checking procedure.
2. Set the monitoring time to a value to match your application.
3. Using this signal, the inverter signals that a forced checking procedure (test stop) is required.
Interconnect this signal with an inverter signal of your choice.
You have set the forced checking procedure (test stop) for the basic functions.
Description
The forced checking procedure (test stop) of the basic functions is an inverter self test. The
inverter checks its circuits to switch off the torque. If you are using the Safe Brake Relay, for
a forced checking procedure, the inverter also checks the circuits of this component.
You start the forced checking procedure each time that the STO function is selected.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
5.11 Setting basic functions
A
Commissioning
131

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents