4.3.2

PROFIsafe telegrams

Two telegrams are available for the data exchange via PROFIsafe between the inverter and
the higher-level controller:
Table 4-1
Overview using PROFINET / PROFIsafe as exam‐
ple
S_STW: Safety control word; S_ZSW: Safety status word
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
PROFIsafe telegrams
4.3 Connection via PROFIsafe
Telegram
Process data (PZD)
PZD1
Telegram 30
S_STW1
PZD 1/1
S_ZSW1
Telegram 900
S_STW1
PZD 2/2
S_ZSW1
The higher-level control selects the safety func‐
tions in the inverter via the control word S_STW1.
The inverter uses the status word S_ZSW1 to re‐
port the status of the safety functions to the con‐
troller.
Telegram 900 of the PROFIsafe profile also in‐
cludes control and status word 5. The inverter
transfers the status of the fail-safe digital inputs
F‑DI 0 ... F‑DI 2 to the control system in status
word S_ZSW5.
Installing
PZD2
---
---
S_STW5
S_ZSW5