detector is power supplied by three pieces of a 3 V Lithium
2400 mAh battery, type 4602. The battery life time is more
than three years.
Up to 16 Wireless photoelectric smoke detectors, type 4601,
can be "connected" to an Addressable Base station for
wireless units, type 4610. Each wireless detector shall be
programmed like the Analog photoelectric smoke detector, type
4301 regarding presentation number (Zone-Address), alarm
text, etc. For more information, see the Technical Description
and the Product Leaflet.
4610 Addressable Base station for wireless units. The Base station
consists of a p.c.b. mounted in a white plastic housing, which
has a great number of cable inlets and mounting holes. It has
fast connectors for the COM loop (in / out) and 24 V DC power
supply respectively. Up to four Base stations can be connected
to a COM loop in the EBL system and up to 16 Wireless
photoelectric smoke detectors (detector address 0-15) can be
"connected" to each Addressable Base station for wireless units,
type 4610. Each Base station shall have a transmission channel
(0-3) selected. The Base station's COM loop address is set on a
DIL-switch. The COM loop address for the wireless detector
respectively is depending on the Base station's COM loop
address, see below. Ext. 24 V DC power supply is required.
For more information, see the Technical Description and the
Product Leaflet.
AAFC Alarm Acknowledgement Facility Control.
box with an alarm indication LED and a non-latching switch
"Press to acknowledge false alarm". One AAFC per AAFC
zone and up to 50 AAFC:s zones can be used. The COM loop
address is set with an Address setting tool (AST) 3314. See
also chapter "Alarm Acknowledgement Facility (AAF)", page
94.

COM loop addresses for Base station and Wireless

detectors

Each Base station takes one COM loop address (012 in the example
below).
Each wireless detector's COM loop address, will be as follows:
Detector
COM loop address
address
0
Base station's COM loop address +1 (e.g. 012+1=013)
1
Base station's COM loop address +2 (e.g. 012+2=014)
..and so on..
51
This unit is available on the Australian market only.
EBL128 Planning Instructions V1.1.x
45