Setup Wireless Detectors (H5/A8) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
27.8
Action
"
"
Menu
Scroll to menu H5.
"
"
Scroll to menu A8
"
"
Rev: -

Setup wireless detectors (H5/A8)

This function can be used by commissioning / service engineer to set a
Base station for wireless units (4620) to one of the following modes:
Register (in order to register one or more wireless detectors 4611 to
the Base station)
Unregister (in order to unregister one or more wireless detectors
4611 from the Base station)
Install (in order to change the communication from normally every
nd
2
minute to every 5
NOTE! To set the Base station to any of the modes above the Base
station has to be in a "Normal state", i.e. not set to any of the modes.
For example, a Base station set to e.g. "Register" mode has to be set
back to "Normal state" before it can be set to any other mode.
For more information, see Technical description MEW01651.
Text in display
H5 Service
A1 Calibration of supervised output
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in control unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
A8 Setup wireless detectors
Set base station mode
Set base station 000000 to
Operating Instructions Fire alarm system EBL512 G3, V2.2.x
th
second, to be used during commissioning, etc.)
Register
Unregister
Install
129
Comments
According to chapter
"Access", see page 88.
Write the technical number
for the Base station. Select
the wanted mode. Press
"
".
Base station in
Register mode is indicated
with "√" and a beep. It
will be shown in the Base
station mode list