Reset Interlocking Output (C3) - Panasonic EBL128 User Manual

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01624 Rev: -
10.3

Reset interlocking output (C3)

Not available for users with access level / type "Information only".
Interlocking output activated via its control expression and with
latching output selected (in EBLWin): The output has to be reset via
this menu (C3).
Interlocking output activated via its control expression and with
latching output not selected: The output can be reset via this menu
(C3).
Interlocking output activated via menu C2 has to be reset via this
menu (C3).
If there are no interlocking outputs to reset,
--- List is empty --- will be shown.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "9") to menu H9.
H9 Interlocking outputs and inputs
Press "A" to sub menu C1.
C1 Activated interlocking outputs / inputs
Scroll (or press "3") to menu C3.
C3 Reset interlocking output
Press "A". This is a list in which you can scroll. Select the Area –
Point for the interlocking output to be reset. Press "A" to reset the
output or press "Return" (P9) to menu C3.
Press "A". If more interlocking outputs shall be reset do as above, if
not press "Return" to menu C3.
Scroll to another menu or press "Return" to menu H9. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual
33