5.5.1
5.5.2
board address (0-7) is set with jumpers (JP1-JP3) on the I/O Matrix
board respectively.
Up to four I/O Matrix boards can be used and up to eight if no
expansion boards of types 4580, 4581 and 4583 are used. but max.
two I/O Matrix boards of the types Generic and Zone respectively.
In EBL128 can totally up to 200 outputs be used, including all kinds
of outputs.
For more information (e.g. application board type selected via jumpers
JP4-JP5), see the I/O Matrix board 4582, Technical description
MEW00914.
Each I/O Matrix board has to be programmed via Win128
regarding:
Address, set via jumpers "JP1-JP3", see Figure 5, page 23.
Type of board (Generic / Fan control / Zone control)
LED test on Input 15 or no LED test on Input 15
The 4582 board has 48 LED outputs and 16 switch inputs (0-15).
Depending on if the Application board is of the type Generic, Fan or
Zone, the outputs and inputs are programmed differently.

Generic

Used for application board type Generic.
Each output (0-47) has to be added and programmed via Win128
regarding:
Output no. (0-47)
Properties like for any programmable relay output.
Each input (0-15) has to be added and programmed via Win128
regarding:
Input no. (0-15)
Type (of input)
Properties (e.g. zone-address, alarm text) like for any
programmable input.

Fan control

Used for application board type Fan control.
28
Each Fan control
(0-3) has to be added programmed via Win128.
Each Fan control (0-3) contains four Fan control panels for control of
one fan each.
For each fan, one COM loop unit, I/O unit for fan control 3361, has
to be added and programmed via Win128 regarding:
28
The Fan control is only available on the Australian market.
EBL128 Planning Instructions V1.1.x
28