Operating Instructions Fire alarm system EBL512 G3, V2.2.x
Replacing a TLON connection
board and/or the Main board
By the TLON network programming, some unique data will be stored
in a memory on the 5090 TLON connection board and some will be
stored in a memory on the 5010 main board.
Replacing only a TLON connection board 5090
After replacing the board:
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
In TLON Manager version 2.0 do "Replace" and "Update" ("Save" is
aut. done).
Replacing both a TLON connection board 5090 and also the Main
board 5010
After replacing the boards:
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
In TLON Manager version 2.0 do "Replace" and "Update" ("Save" is
aut. done).
Replacing only the Main board 5010
After replacing the main board, put back the TLON connection
board(s) in the same position as on the replaced main board:
In TLON Manager version 1.2 do "Update" and "Save".
In TLON Manager version 2.0 do "Update" ("Save" is aut. done).