Expansion Board Address Setting; Zones Expansion Board 4580 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
5.1
Board
address
0
1
2
3
4
5
6
7
5.2

Expansion board address setting

The expansion board address is set via jumpers on the expansion
board respectively.
4580, 4581 and 4583
JP2
JP3
Open
Open
Shunted
Open
Open
Shunted
Shunted
Shunted
Open
Open
Shunted
Open
Open
Shunted
Shunted
Shunted
Figure 5.
Expansion boards 4580 - 4583.
expansion board address setting.

8 zones expansion board 4580

NOTE! P.C.B. NO. 9287-2B and 9287-3A exists. When 9287-3A is
required is indicated below.
Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5 above.)
The 4580 board has eight conventional zone line inputs (0-7) intended
for conventional detectors. In the last alarm point on each zone line,
an end-of-line device has to be connected, depending on the selected
"Type of zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing 128-30.
Each zone line input has to be programmed via Win128 regarding:
Type of zone line input (see below), depending on detectors / end-
of-line device (capacitor or resistor), i.e. different threshold levels
etc.
Alarm at short circuit / Not alarm at short circuit (i.e. if short-
circuit on the zone line shall generate a fault or a fire alarm)
Zone number (no address)
Fire alarm delay / No fire alarm delay
Text (Alarm text when required)
Alert annunciation time channel
Disablement time channel
EBL128 Planning Instructions V1.1.x
JP4
JP1
Open
Open
Open
Shunted
Open
Open
Open
Shunted
Shunted
Open
Shunted
Shunted
Shunted
Open
Shunted
Shunted
23
4582
JP2
JP3
Open
Open
Open
Open
Shunted
Open
Shunted
Open
Open
Shunted
Open
Shunted
Shunted
Shunted
Shunted
Shunted
Jumpers for