Algorithm setting via menu H4/U5

NOTE! Algorithm setting via menu H4/U5 is only valid for the
"British Standard Marine Application" convention.
The alarm algorithm can be set (changed) via menu H4/U5 for the
following detectors:
3304 in NORMAL mode
3308 / 3309 in NORMAL mode
3316 in NORMAL mode (the "Decision algorithm" is not possible to
use)
No alternative algorithm can be used.
No values (offset, level, etc.) can be set via menu H4/U5 (i.e. these
values have to be set via Win512).
The "Short name" (set in Win512) can be < 5 characters.
When scrolling the message "Please Wait....." might be shown for " a
second" and "No more sensors found in the system" (before the lowest
and after the highest possible technical number in the system).
NOTE! If an algorithm is set (changed) via menu H4/U5, the site
specific data (SSD) in the c.i.e. is not equal to the SSD file
downloaded from Win512, i.e. a back up is required to update the
SSD file (xxxxxx.512).
If an algorithm is set (changed) via menu H4/U5, the information in
menu H5/A4 will be changed from "Downloaded: xxxx" to "Modified
by CU: xxxx".
Follow the instructions for 3304, 3308 / 3309 and 3316 respectively: