8
PARAMETER SETTINGS
Configure the following parameter settings.
• Module parameter setting of the master station
Page 64 Module Parameter Setting of the Master Station
• Module parameter setting (safety remote I/O module)
Page 67 Module Parameter Setting
Overview of the parameter setting procedure
The overview of the parameter setting procedure is shown below.
1.
Preparation
Perform the following before parameter settings.
• Configure the system.
• Start the engineering tool.
• Set the Safety CPU to the TEST MODE.
For details on the TEST MODE of the Safety CPU, refer to the following.
 MELSEC iQ-R CPU Module User's Manual (Application)
2.
Network Configuration Settings
Write the network configuration settings to the Safety CPU.
Page 65 Module parameter setting procedure
3.
Parameter Processing of Slave Station
Perform the parameter processing of slave station.
Page 67 Module parameter setting procedure
Step 1 to 7
4.
Safety Communication Setting
Write the safety communication setting of the master station to the Safety CPU.
Page 67 Module parameter setting procedure
Step 8 to 12
5.
Checking the position of the setting target module
Perform the checking of the position of the safety remote I/O module where the parameters are set.
Page 67 Module parameter setting procedure
Step 13 to 18
6.
Safety module validation
Switch the safety remote I/O module to the state where safety communications are enabled (safety drive mode).
Page 67 Module parameter setting procedure
Step 19 to 23
*1 Perform the operations to all safety remote I/O modules connected.
8 PARAMETER SETTINGS
62
*1
*1
*1