Mitsubishi Electric MELSEC iQ-R Series User Manual page 84

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

When the LINK LED turns off
Check item
Are Ethernet cables normal?
Do the switching hub and other stations in the system normally
operate?
If link-up processing is repeated due to a condition of a device on the line, it may take a longer time for the
LINK LED to turn on.
This phenomenon may be eliminated by changing the module PORT into which the Ethernet cable is
connected (example: PORT1  PORT2).
When the SAFETY LED turns off
Check item
Have parameters been set to the safety remote I/O module?
Has the safety communication setting been configured?
Has the safety module validation been performed?
Has the safety station interlock of the Safety CPU been canceled?
Has any error occurred?
Is the operating ambient temperature within the specified range?
10 TROUBLESHOOTING
82
10.1 Checking the LEDs
Action
• Check that 1000BASE-T-compliant Ethernet cables are used.
 User's manual for the master/local module used
• Check that the station-to-station distance is 100m or less.
• Check that the Ethernet cables are not disconnected.
• Check that a 1000BASE-T-compliant switching hub is used.
 User's manual for the master/local module used
• Check that the power supplies of the switching hub and other stations are turned on.
Action
Set the parameters of the safety remote I/O module.
Page 67 Module parameter setting procedure
Configure the safety communication setting. Then, write the parameters to the
programmable controller. For the safety communication setting, refer to the following.
 User's manual for the CPU module used
Perform the safety module validation using the engineering tool.
Fully check the wiring and connection, and cancel the safety station interlock of the
Safety CPU. For the safety station interlock, refer to the following.
 User's manual for the CPU module used
Identify the error factor with the engineering tool and take corrective actions.
Set the operating ambient temperature within the range of general specifications.
Page 19 General Specifications