Safety Standards; Safety Parameters - Mitsubishi Electric MELSEC iQ-R Series User Manual

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

5.2

Safety Standards

Observe the following safety standards.
Region
Global
Europe
North America
5.3

Safety Parameters

The following table lists safety parameters of the safety remote I/O module.
Item
*1
PFDavg
*1
PFH
DCavg
MTTFd
MTBF
*1 Proof test interval is 20 years (module exchange interval).
5 SYSTEM CONFIGURATION
34
5.2 Safety Standards
Standard
IEC 61508: 2010, IEC 62061: 2012, ISO 13849-1
IEC 61131-2
IEC 61000-6-2, IEC 61000-6-4
IEC 61784-3
IEC 60204-1
IEC 61326-3-1
EN ISO13849-1
EN 61131-2
EN 61000-6-2, EN 61000-6-4
UL 61010-1, UL 61010-2-201
NZ2GFS12A2-16DTE
-4
4.0710
-9
4.7010
96.28%
108 years
195.7 years (40)
NZ2GFS12A2-14DT
-4
4.0710
-9
4.6910
96.24%
109 years
207.4 years (40)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gfs12a2-14dtNz2gfs12a2-16dte

Table of Contents