INSTALLATION AND WIRING
This chapter describes the installation and wiring of the safety remote I/O module.
6.1

Setting the Station Number

Setting the station number with the station number setting switch

Setting procedure
Set a station number with the station number setting switch on the front of the module. The setting value of the station number
becomes valid when the module is powered on. Thus, set the station number when the module is powered off.
*1 When operating the station number setting switch, use a flathead screwdriver with 3.5mm or less width of the tip.
*2 For the tightening torque range of the screw for the station number setting switch cover, refer to the following.
Page 36 Tightening torque
1.
Loosen the screw for the station number setting switch
cover with a screwdriver and open the cover.
2.
*1
Set a station number.
• The hundreds and tens places of the station number are set with x10.
• The ones place of the station number is set with x1.
3.
After setting the station number with the station number
setting switch, always close the station number setting
switch cover and tighten the screw for the cover with a
*2
screwdriver.
When the cover is open or the screw has
not been tightened properly, waterproof performance is
lost.