Mitsubishi Electric MELSEC iQ-R Series User Manual page 125

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error history clear command
The error history stored in the module is cleared.
b15
b14
b13
b12
0 (fixed)
(1) 0: Not commanded, 1: Commanded
■Remote buffer memory address
Name
Error history clear command
■Operation of error history clear
When Error history clear command (address: 1000H) is set to Commanded (1), an error history is cleared.
Stored condition of
an error history
Error history clear command
(address: 1000H)
Error history clear completed
(address: 1001H)
■Default value
The default value is Not commanded (0).
Error history clear completed
This remote buffer memory area shows whether the error history stored in the module is cleared or not.
b15
b14
b13
b12
0 (fixed)
(1) 0: Not performed, 1: Completed
■Remote buffer memory address
Name
Error history clear completed
■Operation of error history clear
When the error history clear is completed, Error history clear completed (address: 1001H) is turned to Completed (1).
For the timing when the bit turns to Not performed (0)  Completed (1)  Not performed (0), refer to the following.
Page 123 Error history clear command
■Default value
The default value is Not performed (0).
b11
b10
b9
b8
Controlled by the safety remote I/O module
Controlled by the program
An error history is stored
Not commanded (0)
Not performed (0)
b11
b10
b9
b8
b7
b6
b5
b4
Address
1000H
An error history is not stored
Commanded (1)
Completed (1)
b7
b6
b5
b4
Address
1001H
Appendix 4 Remote Buffer Memory
b3
b2
b1
b0
(1)
Not commanded (0)
Not performed (0)
b3
b2
b1
b0
(1)
APPX
123