Input ON delay
Set the delay time of input OFFON.
■Setting specifications
Address
010BH+3n
(n: 0 to 11)
• When "Wiring selection of input" is set to "1: Double wiring (NC/NC)" or "2: Double wiring (NC/NO)", set the
same value as Xn for Xn+1, the partner of Xn.
• When "Input mode setting" is set to "1: Not used", this parameter will be ignored.
Input OFF delay
Set the delay time of input ONOFF.
■Setting specifications
Address
010CH+3n
(n: 0 to 11)
• When "Wiring selection of input" is set to "1: Double wiring (NC/NC)" or "2: Double wiring (NC/NO)", set the
same value as Xn for Xn+1, the partner of Xn.
• When "Input mode setting" is set to "1: Not used", this parameter will be ignored.
Input mode setting
Set the input setting of the safety remote I/O module in increments of one point. Also set whether or not to execute the input
dark test.
■Setting specifications
Address
010DH+3n
(n: 0 to 11)
• For unused input terminals, set "Input mode setting" to "1: Not used".
• When "Wiring selection of input" is set to "1: Double wiring (NC/NC)" or "2: Double wiring (NC/NO)", set the
same value as Xn for Xn+1, the partner of Xn.
APPX
120
Appendix 4 Remote Buffer Memory
Name
Input ON delay X0 to XB
Name
Input OFF delay X0 to XB
Name
Input mode setting X0 to XB
Setting range
0 to 1000 (ms) (default value: 5)
Setting range
0 to 1000 (ms) (default value: 5)
Setting range
1: Not used (default)
2: Input dark test execution
3: Input dark test non-execution