Error codes related to CC-Link IE Field Network

This section describes CC-Link IE Field Network error codes. Communication errors refer to CC-Link IE Field Network
communication related errors and safety communication related errors. The ERR. LED does not turn on when a
communication error occurs.
Communication errors of CC-Link IE Field Network are classified into the following two error types depending on the operation
of the D LINK LED performed at an error, and troubleshooting differs for each error type.
• Page 100 Communication errors where the D LINK LED flashes or turns off
• Page 101 Communication errors where the D LINK LED does not change
Communication errors where the D LINK LED flashes or turns off
The following table lists the communication errors of CC-Link IE Field Network where the D LINK LED flashes or turns off at
an error. Troubleshoot these errors with the CC-Link IE Field Network diagnostics of the engineering tool.
Error code
Classification Error name
(hexadecimal)
D0E0H
Communication
error
D0E1H
Communication
error
D0E2H
Communication
error
D0E3H
Communication
error
D72AH
Communication
error
10 TROUBLESHOOTING
100
10.7 Error Code List
Description and cause
Station type
The module parameter of the
mismatch
master station is incorrect or
outside the range.
Own station
The module parameter of the
reserved
master station is incorrect or
outside the range.
Station No.
The station number setting
already in use
switch is incorrect.
(own station)
Own station No.
The module parameter of the
out of range
master station is incorrect or
outside the range.
Station number
A station number out of range
switch out of
(a value other than 1 to 120)
range
has been set.
Action
Change the station type of the module to the remote device
station in the "Network Configuration Settings" of the master
station.
• In the "Network Configuration Settings" of the master station,
cancel the reserved station specification.
• Change the station number of the module to a station number
that is not reserved.
• Set a unique station number.
• After taking the above action, power off and on or reset all the
stations where this error was detected.
Add the station information of the module in the "Network
Configuration Settings" of the master station.
Set the station number within the allowable range.