Restart the safety remote I/O module. The SAFETY LED turns on and the mode shifts to the safety drive mode.
23.
Perform the operations from "Safety module validation" to the restart of the safety remote I/O module for all safety
remote I/O modules connected.
"Safety module validation" is cancelled if the following situations arise after the validation performance.
• The parameters have been set again.
• A parameter data error has occurred.
When the safety remote I/O module where "Safety module validation" has been performed is connected to the
different system, the SAFETY LED turns off even though the validation of the safety remote I/O module is not
cancelled. Therefore, perform again "Parameter write" and "Safety module validation".

Module parameter list

This section shows lists of the module parameters of the safety remote I/O module. The following parameters cannot be set
from a program.
• Items to input from the pull-down list
Select a setting value from the pull-down list.
• Items to input in the text box
Input a numerical value within "Setting Range" as a setting value.
8 PARAMETER SETTINGS
72
8.2 Module Parameter Setting