Mitsubishi Electric MELSEC iQ-R Series User Manual page 27

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Applicable waterproof
For power supply
connector
For I/O
Y-branch connector
for I/O
For communications
Cyclic transmission
RX/RY points
RWr/RWw points
SA\X / SA\Y points
Communication cable
Module power supply
Voltage
Current (current
consumption)
Protection function
Max. current
Weight
*1 When using the test pulse output for the power supply for input device, use double insulation cables depending on applications used and
the safety category (SIL/CAT) required.
NZ2GFS12A2-14DT
Input specifications
Page 14 Recommended Connector List
80 points
16 points
SA\X: 28 points
SA\Y: 4 points
An Ethernet cable that meets the 1000BASE-T standard: Category 5e or higher (double shielded, STP),
straight cable
24VDC (ripple ratio: 5% or less) (allowable voltage range: 20.4 to 28.8VDC)
190mA
Module power supply overvoltage protection function, module power supply overcurrent protection function
8A
0.89kg
Output specifications
3 SPECIFICATIONS
3.2 Performance Specifications
3
25