3.2

Performance Specifications

NZ2GFS12A2-16DTE safety remote I/O module
Item
Station type
Number of input points
Rated input voltage
Rated input current
Max. number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input type
Input resistance
Input circuit response
time
Safety remote station input response time
Safety refresh response processing time
Power supply current for input device
Number of output points
Rated load voltage
Load power supply
Max. load current
Max. inrush current
Leakage current at OFF
Max. voltage drop at ON
Protection function
Double output type
Output circuit
response time
Safety remote station output response time
Surge suppressor
Isolation method
Withstand voltage
Isolation resistance
Protection degree
Wiring method for common
Interval of the input diagnostic function
execution
Interval of the output diagnostic function
execution
3 SPECIFICATIONS
20
3.2 Performance Specifications
NZ2GFS12A2-16DTE
Input specifications
Remote device station
Single wiring: 12 points
Double wiring: 6 points
24VDC (ripple ratio: 5% or less) (allowable voltage
range: 20.4 to 28.8VDC)
6mA TYP. (24VDC)
100%
11VDC or higher / 2mA or higher (compliant with IEC
61131-2 Standard digital input type 3)
5VDC or lower / 1.5mA or lower (compliant with IEC
61131-2 Standard digital input type 3)
Negative common
Approx. 4k
OFF  ON
0.5ms or less (24VDC)
ON  OFF
1.5ms or less (24VDC)
Input circuit response time + Input ON/OFF delay
setting
(0 to 1000ms in 1ms steps)
(Initial setting: 5ms)
10ms
*1
0.4A/1 terminal
Protection function
Max. current
OFF  ON
ON  OFF
Non-isolation
500VAC for 1 minute between all DC external terminals and the ground
10M or higher between all DC external terminals and the ground (500VDC isolation resistance tester)
IP67
Input 12 points/common
12ms maximum
2s maximum
Output specifications
Single wiring: 4 points
Double wiring: 2 points
24VDC (ripple ratio: 5% or less) (allowable voltage
range: 20.4 to 28.8VDC)
Load power supply overvoltage protection function,
load power supply overcurrent protection function
8A
1.0A/point
Current is limited by the overload protection function.
0.1mA or less
1.0VDC or lower
Output overload short circuit protection
Source + Source type
10ms
10ms
Output circuit response time
Zener diode
Photocoupler isolation
Output 4 points/common

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gfs12a2-14dtNz2gfs12a2-16dte

Table of Contents