Wiring selection of input
Set the input wiring method in increments of one point.
■Setting specifications
Address
012FH+2n
(n: 0 to 5)
b15
b14
b13
b12
Wiring selection of input X1/X3/X5/X7/X9/XB
Values for both Xn (n: even number) and Xn+1 are set at the same time.
Double input discrepancy detection time
Set the double input discrepancy detection time in increments of two points. Note that settings are done in units of words.
■Setting specifications
Address
0130H+2n
(n: 0 to 5)
When "Wiring selection of input" is set to "3: Single wiring" and "Input mode setting" is set to "1: Not used", this
parameter will be ignored.
Name
Wiring selection of input X0/X1 to XA/XB
b11
b10
b9
b8
Name
Double input discrepancy detection time X0/X1 to
XA/XB
Setting range
1: Double wiring (NC/NC) (default)
2: Double wiring (NC/NO)
3: Single wiring
b7
b6
b5
b4
Wiring selection of input X0/X2/X4/X6/X8/XA
Setting range
10 to 30000 (ms) (default value: 10)
Appendix 4 Remote Buffer Memory
b3
b2
b1
b0
APPX
121
A