Mitsubishi Electric MELSEC iQ-R Series User Manual page 76

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Input setting
Wiring selection of input
Set all the items of the parameters displayed. If any item is left blank, the parameters cannot be written to the
safety remote I/O module.
8 PARAMETER SETTINGS
74
8.2 Module Parameter Setting
Input OFF delay X0
Input OFF delay X1
Input OFF delay X2
Input OFF delay X3
Input OFF delay X4
Input OFF delay X5
Input OFF delay X6
Input OFF delay X7
Input OFF delay X8
Input OFF delay X9
Input OFF delay XA
Input OFF delay XB
Input mode setting X0
Input mode setting X1
Input mode setting X2
Input mode setting X3
Input mode setting X4
Input mode setting X5
Input mode setting X6
Input mode setting X7
Input mode setting X8
Input mode setting X9
Input mode setting XA
Input mode setting XB
Wiring selection of input X0/X1
Wiring selection of input X2/X3
Wiring selection of input X4/X5
Wiring selection of input X6/X7
Wiring selection of input X8/X9
Wiring selection of input XA/XB
Double input discrepancy detection time X0/X1
Double input discrepancy detection time X2/X3
Double input discrepancy detection time X4/X5
Double input discrepancy detection time X6/X7
Double input discrepancy detection time X8/X9
Double input discrepancy detection time XA/XB
Setting range
0 to 1000 (ms) (default value: 5)
1: Not used (default)
2: Input dark test execution
3: Input dark test non-execution
1: Double wiring (NC/NC) (default)
2: Double wiring (NC/NO)
3: Single wiring
10 to 30000 (ms) (default value:
10)
Reference
Page 120 Input OFF delay
Page 120 Input mode setting
Page 121 Wiring selection of
input
Page 121 Double input
discrepancy detection time