Mitsubishi Electric MELSEC iQ-R Series User Manual page 54

Cc-link ie field network waterproof/dustproof remote i/o module (with safety functions)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Combination of double outputs (source + sink connection)
Safety remote output (SA\Y0
to SA\Y3)
*1
SA\Ym
SA\Ym+1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
*1 m: Safety device address (even number from 0 to 1) assigned to the master station
*2 p: 0, 1
■States of safety remote outputs (SA\Y0, SA\Y1) for Y0 and Y1 (double wiring (source + source
connection))
SA\Y0
SA\Y1
Output terminal: Y0
Output terminal: Y1
(1) When double outputs (source + source) are in the discrepancy state (SA\Y0 and SA\Y1 are different), Y0 and Y1 are off.
(2) When double outputs (source + source) are on (SA\Y0 and SA\Y1 are on), Y0 and Y1 are on.
If double outputs are in discrepancy state, a minor error (0207H: I/O data error) occurs.
Setting procedure
Set the output wiring selection in "Wiring selection of output" from the "Parameter Processing of Slave Station" window of the
engineering tool.
For the procedure to display the "Parameter Processing of Slave Station" window, refer to the following.
Page 67 Module parameter setting procedure
■Wiring selection of output (NZ2GFS12A2-16DTE)
Item
Wiring selection of output Yn/Yn+1
(n: 0, 2)
■Wiring selection of output (NZ2GFS12A2-14DT)
Item
Wiring selection of output Yn
(n: 0, 1)
When "Wiring selection of output" is set to "2: Single wiring", both Yn and Yn+1 are single wiring.
7 FUNCTIONS
52
7.2 Output Function
Output terminal state
*1
*2
Yp+
Yp-
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
Safety output status (SA\X18 to
SA\X1B)
*2
*1
SA\X18+m
ON
OFF
OFF
ON
Discrepancy state
ON
(1)
Setting range
1: Double wiring (default)
2: Single wiring
Setting range
1: Double wiring (default)
I/O LED status
*1
*2
SA\X18+m+1
Yp+
ON
Off
OFF
Red
OFF
Red
ON
Green
Discrepancy state
ON
ON
OFF
ON
ON
(2)
(1)
*2
Yp-
Off
Red
Red
Green

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2gfs12a2-14dtNz2gfs12a2-16dte

Table of Contents