6. Parameter setting for DeviceNet serial I/O board
6.1
Parameter setting for DeviceNet serial I/O board
[Procedure]
1) Press the
Chapter
2
2) Press the
parameter setting mode.
The option boards installed in the controller are displayed in order on the PB screen.
SYSTEM>PARAM>OP.BRD V8.63
1.DIO_N(1) VALID
2. −−−
3.D_Net(M1/500k) VALID
4. −−−
SELECT
Option boards installed into the option slots are displayed on the PB screen.
Type
Option DIO
serial I/O
Network
YC-Link
3) In "sYsTEM>PARAM>OP. BRD" mode, select the "D_Net" with the cursor (↑/↓) keys
and press the
SYSTEM>PARAM>OP.BRD>SELECT V8.63
1.board condition VALID
2.remote cmd / IO cmd(SI05) VALID
3.Output MSG to SOW(1) INVALID
4.IO size Large
EDIT JUMP
2-10
(PARAM) key in "sYsTEM" mode to enter "sYsTEM>PARAM" mode.
F 1
(OP. BRD) key in "sYsTEM>PARAM" mode to enter the option board
F 5
Display
An option DIO board of NPN specifications is installed. The number in
DIO_N(n)
parentheses is an ID number.
An option DIO board of PNP specifications is installed. The number in
DIO_P(n)
parentheses is an ID number.
A CC-Link unit is installed. Letters in parentheses indicate a station
CCLnk(n/m)
number "n" and a communication speed "m".
A DeviceNet unit is installed. Letters in parentheses indicate a MAC ID
D_Net(n/m)
number "n" and communication speed "m".
A Profibus unit is installed. Letters in parentheses indicate a station
Profi(n/m)
address "n" and communication speed "m".
E_Net
An Ethernet unit is installed.
A YC-Link unit is installed. Letters in parentheses indicate a station
YCLnk(Mn)
number "n".
(sELECT) key.
F 1
v 1.23M
Meaning
v 1.23M