3. Setting the DeviceNet compatible module

To connect the DeviceNet system specification controller to the DeviceNet system, the MAC
ID and communication speed must be set with the rotary switch on the DeviceNet compatible
module. Carry out the operations explained in section 2.1 to confirm the current MAC ID and
communication speed settings.
3.1

Setting the MAC ID

Using the rotary switches MsB and LsB in front of the DeviceNet compatible module, set the
MAC ID of the robot controller in the DeviceNet system.
NOTE
The MAC ID for the DeviceNet system can be set in the range of 0 to 63.
WARNING
WHEN sETTING THE MAC ID, COMPLETELY sHUT OFF THE POWER sUPPLIED TO
THE ROBOT CONTROLLER.
[Procedures]
1. Check the MAC ID of the robot controller in the DeviceNet system.
The MAC ID must be set between 0 and 63.
2. Using a precision flathead screwdriver, set the 2nd digit of the MAC ID on rotary switch
MsB.
3. In the same manner, set the 1st digit on rotary switch LsB.

3. Setting the DeviceNet compatible module

MSB
LSB
Front of the unit
Chapter
2
2-3