Connecting The Grounding Wire With The Grounding Terminal; Figure 62: Stripping The Stranded Grounding Wire; Figure 63: Attaching The Stranded Grounding Wire To The Grounding Terminal - Allied Telesis AT-SBx908 Installation Manual

Table of Contents

Advertisement

Connecting the Grounding Wire with the Grounding Terminal

To attach a grounding wire with the grounding terminal provided with the
power supply, perform the following procedure:
1. Prepare an adequate length of stranded 10 AWG grounding wire by
stripping it as shown in Figure 62.
Figure 62. Stripping the Stranded Grounding Wire
Note
You must use stranded wire when using the grounding terminal to
connect the ground wire to the grounding post. You may not use
solid wire.
2. Insert the grounding wire into the grounding terminal provided with the
power supply and use a crimping tool to secure it to the grounding
terminal. See Figure 63,
Figure 63. Attaching the Stranded Grounding Wire to the Grounding
3. Verify that the On/Off switch on AT-SBxPWRSYS1-80 DC Power
Supply is in the Off position. Refer to Figure 64 on page 114.
AT-SBx908 GEN2 Installation Guide for Virtual Chassis Stacking
Terminal
113