Installing AT-SBxPWRSYS1-80 DC Power Supplies

This section contains the installation procedure for AT-SBxPWRSYS1-80
DC Power Supplies. For a list of the components that come with the power
supply, refer to "Unpacking AT-SBxPWRSYS1-80 DC Power Supplies" on
page 80.
Warning
The power supply is heavy. Use both hands to lift it. You might injure
yourself or damage the equipment if you drop it.
Caution
The device can be damaged by static electricity. Be sure to follow
proper anti-static precautions when installing the device. Allied
Telesis recommends using a properly grounded wrist strap or other
personal anti-static device and an anti-static mat.
To install AT-SBxPWRSYS1-80 DC Power Supplies in the chassis,
perform the following procedure:
1. Choose a slot for the power supply. The power supply slots are labeled
PSU A and PSU B
If you are installing only one power supply, you may install it in either
slot. Allied Telesis recommends PSU A because that slot does not
come with a blank power supply panel.
2. If there is already a power supply in PSU A, lift the handle on the blank
power supply panel in PSU B and slide the panel from the slot. Refer to
Figure 40 on page 92.
3. Verify that the On/Off switch on the power supply is in the Off position.
Refer to Figure 44 on page 96.
AT-SBx908 GEN2 Installation Guide for Virtual Chassis Stacking