Choosing a
Method for
Attaching the
Power Wires
Connecting the
DC Power Wires
with the Straight
Terminals
The AT-SBxPWRSYS1-80 DC Power Supply comes with the two sets of
power wire terminals, shown in Figure 74. You may use either set to
connect the positive (+) and negative (-) wires to the terminal block on the
power supply. The straight terminals are used to route the wires above or
below the terminal block. The right angle terminals are used to route the
power wires directly away from the terminal block.
Straight Terminals
Figure 74. Power Wire Terminals
Note
The right angle terminals require the removal of the plastic cover
from the terminal block.
You can also install the wires using bare wires.
Here are the procedures for wiring the positive and negative terminal block
on the power supply:
"Connecting the DC Power Wires with the Straight Terminals" on
page 119
"Connecting the DC Power Wires with the Right Angle Terminals" on
page 127
"Connecting Bare DC Power Wires" on page 133
To use the straight terminals to connect the DC power wires to the positive
and negative terminals on the power supply, perform the following
procedure:
1. Prepare adequate lengths of two stranded 8 AWG power wires by
stripping them as shown in Figure 75 on page 120.
Warning
Do not strip more than the recommended amount of wire. Stripping
more than the recommended amount can create a safety hazard by
leaving exposed wire on the terminal block after installation.  E10
AT-SBx908 GEN2 Installation Guide for Virtual Chassis Stacking