Figure 5-2. Hot Sync Can Bridge Card Connections - Eaton Power Xpert 9395 Installation And Operation Manual

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Figure 5-2. Hot Sync CAN Bridge Card Connections

Table 5-1. Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
Name
1
Alarm
2
Alarm Return
3
Alarm Relay NC
4
Alarm Relay Com
5
Alarm Relay NO
6
TX
7
TX
8
CAN L
9
Can H
10
Shield
®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status
Alarm
Description
Programmable UPS alarm. Activated by a remote dry contact closure.
Alarm Relay NC Normally-closed contact opens when UPS is on bypass.
Bypass contact return.
Normally-open contact closes when UPS is on bypass.
RMP II, RIM II, and SCM II connections.
CAN input for parallel operation.
P-164000563—Rev 04 www.eaton.com/powerquality
Installing Options and Accessories
5-3

Advertisement

Table of Contents
loading

Table of Contents