UPS Installation Plan and Unpacking
Table 3-4. 480V Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Eaton 9395P-300/300
(CSS or IOM)
Eaton 9395P-300/275
(CSS or IOM)
Eaton 9395P-300/250
(CSS or IOM)
Eaton 9395P-300/225
(CSS or IOM)
Eaton 9395P-300/200
(CSS or IOM)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
Table 3-5. 575V, 600V Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Eaton 9395P-300/300
(CSS or IOM)
Eaton 9395P-300/275
(CSS or IOM)
Eaton 9395P-300/250
(CSS or IOM)
Eaton 9395P-300/225
(CSS or IOM)
Eaton 9395P-300/200
(CSS or IOM)
Eaton 9395P-300/300
(CSS or IOM)
Eaton 9395P-300/275
(CSS or IOM)
Eaton 9395P-300/250
(CSS or IOM)
Eaton 9395P-300/225
(CSS or IOM)
Eaton 9395P-300/200
(CSS or IOM)
NOTE CSS = Continuous Static Switch; IOM = Input Output Module
®
3-4
Eaton
Power Xpert
Input/Output
Rating
Voltage
300 kVA
480/480
300 kW
275 kVA
480/480
275 kW
250 kVA
480/480
250 kW
225 kVA
480/480
225 kW
200 kVA
480/480
200 kW
Input/Output
Rating
Voltage
300 kVA
575/575
300 kW
275 kVA
575/575
275 kW
250 kVA
575/575
250 kW
225 kVA
575/575
225 kW
200 kVA
575/575
200 kW
300 kVA
600/600
300 kW
275 kVA
600/600
275 kW
250 kVA
600/600
250 kW
225 kVA
600/600
225 kW
200 kVA
600/600
200 kW
®
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality
Heat Rejection
Ventilation Required for Cooling Air Exhaust
kW (1000 BTU/hr)
11.5 (39.4)
10.6 (36.1)
Approximately 1180 liter/sec (2500 CFM)
10.3 (31.9)
Approximately 2124 liter/sec (6500 CFM)
7.9 (27.0)
7.0 (24.0)
Heat Rejection
Ventilation Required for Cooling Air Exhaust
kW (1000 BTU/hr)
16.16 (56.60)
15.2 (51.88)
Approximately 1180 liter/sec (2500 CFM)
13.8 (47.17)
Approximately 2124 liter/sec (4500 CFM)
12.4 (42.45)
11.1 (37.73)
16.16 (56.60)
15.2 (51.88)
Approximately 1180 liter/sec (2500 CFM)
13.8 (47.17)
Approximately 2124 liter/sec (4500 CFM)
12.4 (42.45)
11.1 (37.73)
With field installed FI-UPM:
With field-installed UPM:
With field-installed UPM: