Chapter 8

Communication

This chapter describes the communication features of the Eaton Power Xpert 9395P-300 UPS system and
provides information about connecting hardware. For terminal wiring information, see paragraph 3.2.6 and
paragraph 4.7. For location of the customer interface panels and terminals, see Figure 4-5 and Figure 4-10
through Figure 4-13.
8.1
X-Slot Cards
The 9395P-300 UPS system has four standard, factory-installed X-Slot communication bays. See Figure 4-18
on page 4-24 for bay locations. The UPS is compatible with the following X-Slot cards (see Figure 8-1):
Power Xpert Gateway Card - provides a data gateway from the UPS to the Power Xpert software; provides
l
remote monitoring through a Web browser interface, e-mail, and a network management system using
SNMP; connects to a twisted-pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the UPS parameters to a Building Management System (BMS). It has a built-in switching hub
that allows one additional network device to be connected to the network without the requirement of an
additional network drop.
Modbus Card - provides direct integration of UPS information (meters and status) to a Building Management
l
System (BMS) using the Modbus RTU protocol.
Relay Interface Card (AS/400) - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure,
l
Low battery, UPS alarm/OK, or On bypass when interfacing with IBM AS/400 computers, other relay
connected computers, and industrial applications.
Industrial Relay Card (IRC) - indicates the operating status of the UPS system using the customer's
l
monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to
indicate the UPS status. Online, Bypass, Battery, and Alarm modes can be monitored.
Hot Sync CAN Bridge Card - provides connectivity for operational mode control and metering of a parallel
l
system at any UPM in the system. In addition, this card can be used to connect optional system monitoring
devices, such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or a Supervisory
Contact Module II (SCM II) to the UPS.
LAN drops for use with X-Slot connectivity cards must be provided by facility planners or the customer.
For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10). Refer to
the manual supplied with the X-Slot card for user instructions.
Relay Interface Card

Figure 8-1. Optional X-Slot Cards

®
®
Eaton
Power Xpert
Modbus Card
Power Xpert Gateway Card
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
Hot Sync CAN Bridge
Card
Industrial Relay Card
P-164000563—Rev 04 www.eaton.com/powerquality
8-1