PredictPulse
l
management service from Eaton that collects and analyzes data from connected power infrastructure
devices, providing us with the insight needed to make recommendations and take action on your behalf. It's
also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of
eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of alarms and system
performance (load, temperature/humidity, battery health, energy savings and service level) to reduce
downtime risk and expedite repairs. PredictPulse also shares real-time status and trend information via an
online dashboard and smartphone mobile app (Apple and Android), giving subscribers insights about past
and current performance, a list of all active alarms, and asset management data, such as battery date codes,
last and next scheduled service dates, firmware versions. The service notifies customers of critical alarms,
supports remote diagnostics, and facilitates smart dispatch of technicians. PredictPulse requires a Power
Xpert Gateway UPS (PXGX) connectivity card in an X-Slot communication bay and an Environmental
Monitoring Probe (EMP) for battery temperature/humidity monitoring.
See Chapter 8, "Communication" for additional information on monitoring and communication features.
1.5

Battery System

Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead-acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPSs in distributed bypass and parallel systems must use a separate battery system.
Consult the Eaton
Installation Manual (P-164000580) for specifics on battery cabinet usage with the 9395P-300.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
Remote Monitoring and Management Service
®
®
Power Xpert
9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR)
NOTE
The 9395P-300 system can trip a maximum of six battery cabinets total. This applies
to both the 1085 standard and High Rate series batteries. If more than six battery
cabinets in total are needed in a separate UPM battery configuration, DO NOT hook
up the shunt trips.