Eaton Power Xpert 9395 Installation And Operation Manual page 51

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

Table 3-13. 415 Input/Output Ratings and External Wiring Requirements for the One/Two UPM Separate Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Each Battery Disconnect to Each UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
(1) Positive, (1) Negative
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
A
B
NOTE
V
Callout letters
,
Figure 6-5 on page 10 through Figure 6-14 on page 19.
NOTE
V
Bypass wiring data is not applicable to IOM configurations.
Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system
performance and battery run time.
Battery Cable Routing Requirements
Conduit applications:
* Each conduit must have a Positive, Negative, and Ground conductor.
* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required in each conduit.
Raceway applications:
* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).
* There must be a ground cable running in the raceway with the battery cables.
®
®
Eaton
Power Xpert
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual
C
D
,
, and
map to common battery systems. Callout letters
UPS Installation Plan and Unpacking
Rating
Units
50/60 Hz
200
kVA
200
kW
Volts
415/415
Amps
342
A
AWG or
350
kcmil
(2)
(each)
Amps
278
B
AWG or
250
kcmil
(2)
(each)
Total
603
Amps
C
AWG or
500
kcmil
(3)
(each)
Amps
278
D
AWG or
250
kcmil
(2)
(each)
A
C
D
,
, and
map to separate battery systems. See
P-164000563—Rev 04 www.eaton.com/powerquality
Rating
Rating
Rating
50/60 Hz
50/60 Hz
50/60 Hz
250
275
225
225
250
275
415/415
415/415
415/415
385
428
471
500
500
300
(2)
(2)
(3)
313
348
383
300
350
500
(2)
(2)
(2)
603
603
603
500
500
500
(3)
(3)
(3)
313
348
383
300
350
500
(2)
(2)
(2)
3-21