Eaton Power Xpert 9395 Installation And Operation Manual page 44

Hide thumbs Also See for Power Xpert 9395:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Table 3-6. 600V Input/Output Ratings and External Wiring Recommendations for the One/Two UPM Common Battery
Basic Unit Rating
Input and Output Voltage
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
(1) Positive, (1) Negative
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Pole
NOTE
V
Callout letters
Figure 6-5 on page 10 through Figure 6-14 on page 19.
NOTE
V
Bypass wiring data is not applicable to IOM configurations.
Battery Conductor Sizing: Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system
performance and battery run time.
Battery Cable Routing Requirements
Conduit applications:
* Each conduit must have a Positive, Negative, and Ground conductor.
* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required in each conduit.
Raceway applications:
* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).
* There must be a ground cable running in the raceway with the battery cables.
®
3-14
Eaton
Power Xpert
A
B
C
D
,
,
, and
map to common battery systems. Callout letters
®
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality
Rating
Rating
Units
50/60 Hz
50/60 Hz
kVA
200
225
kW
200
225
Volts
600
600
Amps
240
272
A
AWG or
350 (1)
500 (1)
kcmil
or
(each)
2/0 (2)
2/0 (2)
Amps
192
217
B
AWG or
300 (1)
350 (1)
kcmil
or
(each)
1/0 (2)
2/0 (2)
Amps
443
498
C
AWG or
500
500
kcmil
(3)
(each)
Amps
192
217
D
AWG or
300 (1)
350 (1)
kcmil
or
(each)
1/0 (2)
2/0 (2)
A
C
,
, and
Rating
Rating
Rating
50/60 Hz
50/60 Hz
50/60 Hz
250
275
250
275
600
600
300
332
500 (1)
4/0 (2)
4/0 (2)
or
or
or
3/0 (2)
1/0 (3)
1/0 (3)
241
265
500 (1)
500 (1)
4/0 (2)
or
or
or
2/0 (2)
3/0 (2)
1/0 (3)
553
609
500
500
(3)
(3)
(3)
241
265
500 (1)
500 (1)
4/0 (2)
or
or
or
2/0 (2))
3/0 (2)
1/0 (3)
D
map to separate battery systems. See
300
300
600
360
or
289
or
664
500
(3)
289
or