UPS Installation Plan and Unpacking
1.
Carefully inspect the outer packaging for evidence of damage during transit.
Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service
representative immediately.
Ne pas installer une armoire endommagée. Signaler les dommages au transporteur et
communiquer avec un représentant du service Eaton immédiatement.
NOTE
2.
Use a forklift or pallet jack to move the packaged cabinets to the installation site, or as close as possible,
before unpacking. If possible, move the cabinets using the pallet. Insert the forklift or pallet jack forks from
the right side of the pallet (facing the cabinet), between the supports on the bottom of the pallet. If the
cabinets must be moved using the cabinet front or rear fork lift slots, see the caution statement at the
beginning of this procedure.
Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.
Ne pas incliner les armoires d'onduleur à plus de 10 degrés de la verticale puisqu'elles pourraient
se renverser.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft) on each side for
removing the cabinet from the pallet.
The ISBM and UPM sections are shipped with debris shields covering the ventilation grills on top of
the sections (see Figure 4-4). Do not remove the debris shields until installation is complete.
4.
Remove the protective covering from the cabinets.
5.
Remove the packing material, and discard or recycle in a responsible manner.
6.
Inspect the contents for any evidence of physical damage, and compare each item with the Bill of Lading.
If damage has occurred or shortages are evident, contact an Eaton service representative immediately to
determine the extent of the damage and its impact on further installation.
While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful
contaminants. Failure to store and protect the UPS properly may void your warranty.
®
3-36
Eaton
Power Xpert
For the following step, verify that the forklift or pallet jack is rated to handle the
weight of the cabinet (see Table 3-1 for cabinet weight).
®
9395P-300 (300kVA, 300kW) UPS Installation and Operation Manual P-164000563—Rev 04 www.eaton.com/powerquality