Allen-Bradley LOGIX 5000 Reference Manual page 96

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
96
(2)
On the transition to Auto or Cascade/Ratio mode, the instruction sets En-1 =
En.
The instruction disables the zero crossing algorithm and clears ZCDeadband
under these conditions:
during instruction first scan
ZCDeadband ≤ 0
Auto or Cascade/Ratio is not the current mode
PVFaulted is set
PVSpanInv is set
Feedforward Control
Compute CV by summing CV from the zero crossing algorithm with ∆FF. The
value of ∆FF = FF – FFn-1. When FFSetPrevious is set, FFn-1=FFPrevious. This
lets you preset FFn-1 to a specified value before the instruction calculates the value
of ∆FF.
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018