Chapter 1
Process Control Instructions
210
Input Parameters Data
Type
CV3OverrideValue
REAL
CVManLimiting
BOOL
CV1EUMax
REAL
CV2EUMax
REAL
CV3EUMax
REAL
CV1EUMin
REAL
CV2EUMin
REAL
CV3EUMin
REAL
CV1HLimit
REAL
CV2HLimit
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV3 Override value. CV3 set to this value when in
Override mode.
This value should correspond to a safe state
output of the loop.
If value of CV3OverrideValue < 0 or >100, set
unique Status bit and limit value used for CV3.
Limit CV(n), where (n) can be 1, 2, or 3, in Manual
mode. If Manual mode and CVManLimiting is
TRUE, CV(n) will be limited by the CV(n)HLimit
and CV(n)LLimit values.
Maximum value for CV1EU. The value of CV1EU
that corresponds to 100% CV1.
If CVEUMax = CVEUMin, set bit in Status.
Maximum value for CV2EU. The value of CV2EU
that corresponds to 100% CV2.
If CVEUMax = CVEUMin, set bit in Status.
Maximum value for CV3EU. The value of CV3EU
that corresponds to 100% CV3.
If CVEUMax = CVEUMin, set bit in Status.
Minimum value of CV1EU. The value of CV1EU
that corresponds to 0% CV1.
If CVEUMax = CVEUMin, set bit in Status.
Minimum value of CV2EU. The value of CV2EU
that corresponds to 0% CV2.
If CVEUMax = CVEUMin, set bit in Status.
Minimum value of CV3EU. The value of CV3EU
that corresponds to 0% CV3.
If CVEUMax = CVEUMin, set bit in Status.
CV1 high limit value. This is used to set the
CV1HAlarm output. It is also used for limiting CV1
when in Auto mode or in Manual if
CVManLimiting is TRUE.
• If CV1LLimit < 0, if CV1HLimit > 100, if
CV1HLimit < CV1LLimit, set bit in Status.
• If CV1HLimit < CV1LLimit, limit CV1 by using
the value of CV1LLimit.
CV2 high limit value. This is used to set the
CV2HAlarm output. It is also used for limiting CV2
when in Auto mode or in Manual if
CVManLimiting is TRUE.
• If CV2LLimit < 0, if CV2HLimit > 100, if
CV2HLimit < CV2LLimit, set bit in Status.
• If CV2HLimit < CV2LLimit, limit CV2 by using
the value of CV2LLimit.
Values
Valid = 0.0 through 100.0
Default = 0.0
Default = FALSE
Valid = any float
Default = 100.0
Valid = any float
Default = 100.0
Valid = any float
Default = 100.0
Valid = any float
Default = 0.0
Valid = any float
Default = 0.0
Valid = any float
Default = 0.0
Valid = CV1LLimit <
CV1HLimit ≤ 100.0
Default = 100.0
Valid = CV2LLimit <
CV2HLimit ≤ 100.0
Default = 100.0