Allen-Bradley LOGIX 5000 Reference Manual page 170

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
170
CV1Hand
BOOL
CV2Hand
BOOL
CV3Hand
BOOL
DeltaT
REAL
CV1StepSizeUsed
REAL
CV2StepSizeUsed
REAL
CV3StepSizeUsed
REAL
CV1GainTuned
REAL
CV2GainTuned
REAL
CV3GainTuned
REAL
CV1TCTuned
REAL
CV2TCTuned
REAL
CV3TCTuned
REAL
CV1DTTuned
REAL
CV2DTTuned
REAL
CV3DTTuned
REAL
CV1RespTCTunedS
REAL
CV2RespTCTunedS
REAL
CV3RespTCTunedS
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Hand mode indicator for CV1. TRUE
when CV1 in the Hand mode.
Hand mode indicator for CV2. TRUE
when CV2 in the Hand mode.
Hand mode indicator for CV3. TRUE
when CV3 in the Hand mode.
Elapsed time between updates in
seconds.
Actual CV1 step size used for tuning.
Actual CV2 step size used for tuning.
Actual CV3 step size used for tuning.
The calculated value of the internal
model gain for CV1 after tuning is
completed.
The calculated value of the internal
model gain for CV2 after tuning is
completed.
The calculated value of the internal
model gain for CV3 after tuning is
completed.
The calculated value of the internal
model time constant for CV1 after
tuning is completed.
The calculated value of the internal
model time constant for CV2 after
tuning is completed.
The calculated value of the internal
model time constant for CV3 after
tuning is completed.
The calculated value of the internal
model deadtime for CV1 after tuning
is completed.
The calculated value of the internal
model deadtime for CV2 after tuning
is completed.
The calculated value of the internal
model deadtime for CV3 after tuning
is completed.
The calculated value of the control
variable time constant in slow
response speed for CV1 after tuning
is completed.
The calculated value of the control
variable time constant in slow
response speed for CV2 after tuning
is completed.
The calculated value of the control
variable time constant in slow
response speed for CV3 after tuning
is completed.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents