30
Input Parameter
Data
Type
Out2State0
BOOL
Out2State1
BOOL
Out2State2
BOOL
OverrideState
DINT
FB0State0
BOOL
FB0State1
BOOL
FB0State2
BOOL
FB1State0
BOOL
FB1State1
BOOL
FB1State2
BOOL
FB2State0
BOOL
FB2State1
BOOL
FB2State2
BOOL
FB3State0
BOOL
FB3State1
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Output 2 state 0 input. This value determines the value of Output2 when the
device is in the 0 state.
Default is false.
Output 2 state 1 input. This value determines the value of Output2 when the
device is in the 1 state.
Default is false.
Output 2 state 2 input. This value determines the value of Output2 when the
device is in the 2 state.
Default is false.
Override state input. Set this input to indicate the state of the device when in
Override mode.
2 = Device should go to the 2 state
1 = Device should go to the 1 state
0 = Device should go to the 0 state
An invalid value sets the appropriate bit in Status.
Valid = 0 to 2
Default = 0
Feedback 0 state 0 input. This value determines the expected value of FB0 when
the device is in the 0 state.
Default is false.
Feedback 0 state 1 input. This value determines the expected value of FB0 when
the device is in the 1 state.
Default is false.
Feedback 0 state 2 input. This value determines the expected value of FB0 when
the device is in the 2 state.
Default is false.
Feedback 1 state 0 input. This value determines the expected value of FB1 when
the device is in the 0 state.
Default is false.
Feedback 1 state 1 input. This value determines the expected value of FB1 when
the device is in the 1 state.
Default is false.
Feedback 1 state 2 input. This value determines the expected value of FB1 when
the device is in the 2 state.
Default is false.
Feedback 2 state 0 input. This value determines the expected value of FB2 when
the device is in the 0 state.
Default is false.
Feedback 2 state 1 input. This value determines the expected value of FB2 when
the device is in the 1 state.
Default is false.
Feedback 2 state 2 input. This value determines the expected value of FB2 when
the device is in the 2 state.
Default is false.
Feedback 3 state 0 input. This value determines the expected value of FB3 when
the device is in the 0 state.
Default is false.
Feedback 3 state 1 input. This value determines the expected value of FB3 when
the device is in the 1 state.
Default is false.