Allen-Bradley LOGIX 5000 Reference Manual page 213

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Process Control Instructions
Input Parameters Data
Type
CV2HandFBFault
BOOL
CV3HANDFBFault
BOOL
CV1Target
REAL
CV2Target
REAL
CV3Target
REAL
CV1WindupHIn
BOOL
CV2WindupHIn
BOOL
CV3WindupHIn
BOOL
CV1WindupLIn
BOOL
CV2WindupLIn
BOOL
CV3WindupLIn
BOOL
GainEUSpan
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV2HandFB value bad health indicator. If the
CV2HandFB value is read from an analog input,
then CV2HandFBFault will normally be controlled
by the status of the analog input channel.
If CV2HandFBFault is TRUE, it indicates an error on
the input module, set bit in Status.
FALSE = Good Health
CV3HandFB value bad health indicator. If the
CV3HandFB value is read from an analog input,
then CV3HandFBFault will normally be controlled
by the status of the analog input channel.
If CV3HandFBFault is TRUE, it indicates an error on
the input module, set bit in Status.
FALSE = Good Health
Target value for control variable output 1.
Target value for control variable output 2.
Target value for control variable output 3.
CV1Windup high request. When TRUE, CV1 will
not be allowed to increase in value. This signal
will typically be the CV1WindupHOut output from
a secondary loop.
CV2Windup high request. When TRUE, CV2 will
not be allowed to increase in value. This signal
will typically be the CV2WindupHOut output from
a secondary loop.
CV3Windup high request. When TRUE, CV3 will
not be allowed to increase in value. This signal
will typically be the CV3WindupHOut output from
a secondary loop.
CV1 Windup low request. When TRUE, CV1 will
not be allowed to decrease in value. This signal
will typically be the CV1WindupLOut output from
a secondary loop.
CV2 Windup low request. When TRUE, CV2 will
not be allowed to decrease in value. This signal
will typically be the CV2WindupLOut output from
a secondary loop.
CV3 Windup low request. When TRUE, CV3 will
not be allowed to decrease in value. This signal
will typically be the CV3WindupLOut output from
a secondary loop.
ModelGain units in EU or as % of span.
Chapter 1
Values
Default = FALSE
Default = FALSE
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
FALSE = Gain in % of span
213