Allen-Bradley LOGIX 5000 Reference Manual page 164

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
164
CV1ResponseSpeed
DINT
CV2ResponseSpeed
DINT
CV3ResponseSpeed
DINT
CV1ModelInit
BOOL
CV2ModelInit
BOOL
CV3ModelInit
BOOL
Factor
REAL
AtuneCV1Start
BOOL
AtuneCV2Start
BOOL
AtuneCV3Start
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Desired speed of closed loop response
for CV1.
Slow response: ResponseSpeed=0
Medium response: ResponseSpeed=1
Fast response: ResponseSpeed=2.
If ResponseSpeed is less than 0, Slow
response is used. If ResponseSpeed is
greater than 2, Fast response is used.
Desired speed of closed loop response
for CV2.
Slow response: ResponseSpeed=0
Medium response: ResponseSpeed=1
Fast response: ResponseSpeed=2.
If ResponseSpeed is less than 0, Slow
response is used. If ResponseSpeed is
greater than 2, Fast response is used.
Desired speed of closed loop response
for CV3.
Slow response: ResponseSpeed=0
Medium response: ResponseSpeed=1
Fast response: ResponseSpeed=2.
If ResponseSpeed is less than 0, Slow
response is used. If ResponseSpeed is
greater than 2, Fast response is used.
Internal model initialization switch for
CV1. Refer to topic CC Function Block
Model Initialization in CC Function
Block Tuning.
Internal model initialization switch for
CV2. Refer to topic CC Function Block
Model Initialization in CC Function
Block Tuning.
Internal model initialization switch for
CV3. Refer to topic CC Function Block
Model Initialization in CC Function
Block Tuning.
Non-integrating model approximation
factor. Only used for integrating
process types.
Start Autotune request for CV1. Set
True to initiate auto tuning of the CV1
output. Ignored when CV1 is not in
Manual mode. The function block
resets the input to FALSE.
Start Autotune request for CV2. Set
True to initiate auto tuning of the CV2
output. Ignored when CV2 is not in
Manual mode. The function block
resets the input to FALSE.
Start Autotune request for CV3. Set
True to initiate auto tuning of the CV3
output. Ignored when CV3 is not in
Manual mode. The function block
resets the input to FALSE.
Range: 0...2
Default=1
Range: 0...2
Default=1
Range: 0...2
Default=1
Default = FALSE
Default = FALSE
Default = FALSE
Default = 100
Default = FALSE
Default = FALSE
Default = FALSE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents