Allen-Bradley LOGIX 5000 Reference Manual page 160

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
160
Target1stCV
DINT
Target2ndCV
DINT
Target3rdCV
DINT
PVTracking
BOOL
CVTrackReq
BOOL
ManualAfterInit
BOOL
ProgProgReq
BOOL
ProgOperReq
BOOL
ProgCV1AutoReq
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
The CV with top priority to be driven
to its target value.
1=CV1, 2=CV2, 3=CV3
The CV with second highest priority to
be driven to its target value.
1=CV1, 2=CV2, 3=CV3
The CV with third highest priority to
be driven to its target value.
1=CV1, 2=CV2, 3=CV3
SP track PV request. Set TRUE to
enable SP to track PV. Ignored when
in Auto modes. SP will only track PV
when all three outputs are in manual.
As soon as any output returns to Auto,
PVTracking stops.
CV Track request. Set true to enable CV
Tracking when autotune is OFF.
Ignored in Hand and Override mode.
Manual mode after initialization
request.
When TRUE, the appropriate CV(n),
where (n) can be 1, 2, or 3, will be
placed in Manual mode when
CV(n)Initializing is set TRUE unless the
current mode is Override or Hand.
When ManualAfterInit is FALSE, the
CV(n) mode will not be changed.
Program Program Request.
Set TRUE by the user program to
request Program control.
Ignored if ProgOperReq is TRUE.
Holding this TRUE and ProgOperReq
FALSE can be used to lock the function
block into program control.
When ProgValueReset is TRUE, the
function block resets the input to
FALSE.
Program Operator Request.
Set TRUE by the user program to
request Operator control.
Holding this TRUE can be used to lock
the function block into operator
control.
If value of HandFB < 0 or > 100, set
unique Status bit and limit value used
for CV.
Program-Auto mode request for CV1.
Set TRUE by the user program to
request Auto mode.
If value of CV1HandFB < 0 or > 100,
set unique Status bit and limit value
used for CV1.
Valid = 1-3
Default = 1
Valid = 1-3
Default = 2
Valid = 1-3
Default = 3
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents