Statistical Instructions
Function Block
Structured Text
MAXC(MAXC_tag);
Operands
Function Block
Operand
Type
MAXC tag
MAXIMUM_CAPTURE
MAXIMUM_CAPTURE Structure
Input Parameter
Data Type
EnableIn
BOOL
In
REAL
Reset
BOOL
ResetValue
REAL
Output
Data Type
Parameter
EnableOut
BOOL
Out
REAL
Structured Text
Operand
Type
MAXC tag
MAXIMUM_CAPTURE
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Format
Description
Structure
MAXC structure
Description
Enable input. If cleared, the instruction does not execute and outputs are not
updated.
Default is set.
The analog signal input to the instruction.
Valid = any float
Default = 0.0
Request to reset control algorithm. The instruction sets Out = ResetValue as
long as Reset is set.
Default is cleared.
The reset value for the instruction. The instruction sets Out = ResetValue as
long as Reset is set.
Valid = any float
Default = 0.0
Description
Enable output.
The calculated output of the algorithm.
Format
Description
Structure
MAXC structure
Chapter 5
389

Hide quick links: