Operands
Function Block
Operand
Type
HPF tag
FILTER_HIGH_PASS
Input Parameter
Data Type
EnableIn
BOOL
In
REAL
Initialize
BOOL
WLead
REAL
Order
REAL
OversampleDT
REAL
RTSTime
DINT
RTSTimeStamp
DINT
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Format
Description
structure
HPF structure
Description
Enable input. If false, the instruction does not
execute and outputs are not updated.
Default is true.
The analog signal input to the instruction.
Valid = any float
Default = 0.0
Request to initialize filter control algorithm.
When true, the instruction sets Out = In.
Default is false.
The lead frequency in radians/second. If WLead <
minimum or WLead > maximum, the instruction
sets the appropriate bit in Status and limits
WLead.
Valid = see Description section below for valid
ranges.
Default = 0.0
Order of the filter. Order controls the sharpness of
the cutoff. If Order is invalid, the instruction sets
the appropriate bit in Status and uses Order = 1.
Valid = 1 to 3
Default = 1
Execution time for oversample mode.
Valid = 0 to 4194.303 seconds
Default = 0
Module update period for real time sampling
mode
Valid = 1 to 32,767ms
Default = 1
Module time stamp value for real time sampling
mode.
Valid = 0 to 32,767ms
Default = 0
Chapter 3
325