Process Control Instructions
ProgProgReq
BOOL
ProgOperReq
BOOL
ProgCasRatReq
BOOL
ProgAutoReq
BOOL
ProgManualReq
BOOL
ProgOverrideReq
BOOL
ProgHandReq
BOOL
OperProgReq
BOOL
OperOperReq
OperCasRatReq
BOOL
OperAutoReq
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Program Program Request.
Set TRUE by the user program to request
Program control. Ignored if ProgOperReq is
TRUE. Holding this TRUE and ProgOperReq
FALSE can be used to lock the function
block into program control.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Program Operator Request. Set TRUE by the
user program to request Operator control.
Holding this TRUE can be used to lock the
function block into operator control. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Program-Cascade/Ratio mode request. Set
TRUE by the user program to request
Cascasde/Ratio mode. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Program-Auto mode request. Set TRUE by
the user program to request Auto mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Program-Manual mode request. Set TRUE
by the user program to request Manual
mode. When ProgValueReset is TRUE, the
function block resets the input to FALSE.
Program-Override mode request. Set TRUE
by the user program to request Override
mode. When ProgValueReset is TRUE, the
function block resets the input to FALSE.
Program-Hand mode request. Set TRUE by
the user program to request Hand mode.
This value will usually be read as a digital
input from a hand/auto station. When
ProgValueReset is TRUE, the function block
resets the input to FALSE.
Operator Program Request. Set TRUE by the
operator interface to request Program
control. The function block resets this
parameter to FALSE.
Operator Operator Request. Set TRUE by
the operator interface to request Operator
control. The function block will reset this
parameter to FALSE.
Operator-CascadeRatio mode request. Set
TRUE by the operator interface to request
CascadeRatio mode. The function block will
reset this parameter to FALSE.
Operator-Auto mode request. Set TRUE by
the operator interface to request Auto
mode. The function block will reset this
parameter to FALSE.
Chapter 1
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
191