Chapter 1
Process Control Instructions
212
Input Parameters Data
Type
CV1ROCNegLimit
REAL
CV2ROCNegLimit
REAL
CV3ROCNegLimit
REAL
CV1HandFB
REAL
CV2HandFB
REAL
CV3HandFB
REAL
CV1HandFBFault
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV1 rate of change limit, in percent per second.
Rate of change limiting is only used when in Auto
mode or in Manual mode if CVManLimiting is
TRUE. A value of zero disables CV1 ROC limiting.
If value of CV1ROCLimit < 0, set bit in Status and
disable CV1 ROC limiting.
CV2 rate of change limit, in percent per second.
Rate of change limiting is only used when in Auto
mode or in Manual mode if CVManLimiting is
TRUE. A value of zero disables CV2 ROC limiting.
If value of CV2ROCLimit < 0, set bit in Status and
disable CV2 ROC limiting.
CV3 rate of change limit, in percent per second.
Rate of change limiting is only used when in Auto
mode or in Manual mode if CVManLimiting is
TRUE. A value of zero disables CV3 ROC limiting.
If value of CV3ROCLimit < 0, set bit in Status and
disable CV3 ROC limiting.
CV1 HandFeedback value. CV1 set to this value
when in Hand mode and CV1HandFBFault is
FALSE (good health). This value would typically
come from the output of a field mounted
hand/auto station and would be used to generate
a bumpless transfer out of Hand mode.
If value of CV1HandFB < 0 or > 100, set unique
Status bit and limit value used for CV1.
CV2 HandFeedback value. CV2 set to this value
when in Hand mode and CV2HandFBFault is
FALSE (good health). This value would typically
come from the output of a field mounted
hand/auto station and would be used to generate
a bumpless transfer out of Hand mode.
If value of CV2HandFB < 0 or > 100, set unique
Status bit and limit value used for CV2.
CV3 HandFeedback value. CV3 set to this value
when in Hand mode and CV3HandFBFault is
FALSE (good health). This value would typically
come from the output of a field mounted
hand/auto station and would be used to generate
a bumpless transfer out of Hand mode.
If value of CV3HandFB < 0 or > 100, set unique
Status bit and limit value used for CV3.
CV1HandFB value bad health indicator. If the
CV1HandFB value is read from an analog input,
then CV1HandFBFault will normally be controlled
by the status of the analog input channel.
If CV1HandFBFault is TRUE, it indicates an error on
the input module, set bit in Status.
FALSE = Good Health
Values
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Default = FALSE

Hide quick links: