Chapter 1
Process Control Instructions
214
Input Parameters Data
Type
CV1PV1ProcessGain
BOOL
Sign
CV2PV1ProcessGain
BOOL
Sign
CV3PV1ProcessGain
BOOL
Sign
CV1PV2ProcessGain
BOOL
Sign
CV1PV2ProcessGain
BOOL
Sign
CV1PV2ProcessGain
BOOL
Sign
ProcessType
DINT
CV1PV1ModelGain
REAL
CV2PV1ModelGain
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Used only for Autotuning. Sign of the process gain
(Delta PV1/Delta CV1).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV1).
• Reset to indicate a positive process gain
(increase in output causes an increase in P1V).
Used only for Autotuning. Sign of the process gain
(Delta PV1/Delta CV2).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV1).
• Reset to indicate a positive process gain
(increase in output causes an increase in PV1).
Used only for Autotuning. Sign of the process gain
(Delta PV1/Delta CV3).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV1).
• Reset to indicate a positive process gain
(increase in output causes an increase in PV1).
Used only for Autotuning. Sign of the process gain
(Delta PV2/Delta CV1).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV2).
• Reset to indicate a positive process gain
(increase in output causes an increase in PV2).
Used only for Autotuning. Sign of the process gain
(Delta PV2/Delta CV2).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV2).
• Reset to indicate a positive process gain
(increase in output causes an increase in PV2).
Used only for Autotuning. Sign of the process gain
(Delta PV2/Delta CV3).
• Set to indicate a negative process gain
(increase in output causes a decrease in PV2).
• Reset to indicate a positive process gain
(increase in output causes an increase in PV2).
Process type selection for both PV1 and PV2
(1=Integrating, 0=non-integrating)
The internal model gain parameter for CV1 - PV1.
Enter a positive or negative gain depending on
process direction.
If CV1PV1ModelGain = INF or NAN, set bit in
Status.
The internal model gain parameter for CV2 - PV1.
Enter a positive or negative gain depending on
process direction.
If CV2PV1ModelGain = INF or NAN, set bit in
Status.
Values
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = 0
Valid = maximum negative
float −> maximum positive
float
Default = 0.0
Valid = maximum negative
float −> maximum positive
float
Default = 0.0