Process Control Instructions
Status3CV3
DINT
InstructFault
BOOL
PVFaulted
BOOL
PVSpanInv
BOOL
SPProgInv
BOOL
SPOperInv
BOOL
SPLimitsInv
BOOL
SampleTimeTooSmall
BOOL
FactorInv
BOOL
TimingModeInv
BOOL
RTSMissed
BOOL
RTSTimeInv
BOOL
RTSTimeStampInv
BOOL
DeltaTInv
BOOL
CV1Faulted
BOOL
CV2Faulted
BOOL
CV3Faulted
BOOL
CV1HandFBFaulted
BOOL
CV2HandFBFaulted
BOOL
CV3HandFBFaulted
BOOL
CV1ProgInv
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Additional bit mapped CV3 status for
the function block. A value of 0
indicates that no faults have
occurred.
The function block has generated a
fault. Indicates state of bits in
Status1, Status2, and Status3CV(n),
where (n) can be 1, 2, or 3.
A value of 0 indicates that no faults
have occurred. Any parameters that
could be configured with an invalid
value must have a status parameter
to indicate their invalid status.
Process variable PV health bad.
The span of PV inValid, PVEUMax <
PVEUMin.
SPProg < SPLLimit or > SPHLimit.
Limit value used for SP.
SPOper < SPLLimit or > SPHLimit.
Limit value used for SP.
Limits inValid: SPLLimit < PVEUMin,
SPHLimit > PVEUMax, or SPHLimit
< SPLLimit. If SPHLimit < SPLLimit,
then limit value by using SPLLimit.
Model DeadTime / DeltaT must be
less than or equal to 200.
Entered value for Factor < 0.
Entered TimingMode inValid. If the
current mode is not Override or Hand
then set to Manual mode.
Only used when in Real Time
Sampling mode. Is TRUE when
ABS(DeltaT – RTSTime) > 1
millisecond.
Entered RTSTime inValid.
RTSTimeStamp inValid. If the current
mode is not Override or Hand, then
set to Manual mode.
DeltaT inValid. If the current mode is
not Override or Hand then, set to
Manual mode.
Control variable CV1 health bad.
Control variable CV2 health bad.
Control variable CV3 health bad.
CV1 HandFB value health bad.
CV2 HandFB value health bad.
CV3 HandFB value health bad.
CV1Prog < 0 or > 100, or <
CV1LLimit or > CV1HLimit when
CVManLimiting is TRUE. Limit value
used for CV1.
Chapter 1
175