Allen-Bradley LOGIX 5000 Reference Manual page 234

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
234
Output
Data
Parameters
Type
AtuneCV2PV2Win
BOOL
dupFault
AtuneCV3PV2Win
BOOL
dupFault
AtuneCV1PV2Step
BOOL
Size0
AtuneCV2PV2Step
BOOL
Size0
AtuneCV3PV2Step
BOOL
Size0
AtuneCV1PV2Limi
BOOL
tsFault
AtuneCV2PV2Limi
BOOL
tsFault
AtuneCV3PV2Limi
BOOL
tsFault
AtuneCV1PV2InitF
BOOL
ault
AtuneCV2PV2InitF
BOOL
ault
AtuneCV3PV2InitF
BOOL
ault
AtuneCV1PV2EUSp
BOOL
anChanged
AtuneCV2PV2EUSp
BOOL
anChanged
AtuneCV3PV2EUSp
BOOL
anChanged
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV2WindupHIn or CV2WindupLIn is True at start of
CV2 - PV2 Autotuning or during CV2 - PV2
Autotuning. When True, CV2 - PV2 Autotuning is
not started or is aborted.
CV3WindupHIn or CV3WindupLIn is True at start of
CV3 - PV2 Autotuning or during CV3 - PV2
Autotuning. When True, CV3 - PV2 Autotuning is
not started or is aborted.
CV1StepSizeUsed = 0 at start of CV1 - PV2
Autotuning. When True, CV1 - PV2 Autotuning is
not started.
CV2StepSizeUsed = 0 at start of CV2 - PV2
Autotuning. When True, CV2 - PV2 Autotuning is
not started.
CV3StepSizeUsed = 0 at start of CV3 - PV2
Autotuning. When True, CV3 - PV2 Autotuning is
not started.
CV1LimitsInv and CVManLimiting are True at start
of CV1 - PV2 Autotuning or during CV1 - PV2
Autotuning. When True, CV1 - PV2 Autotuning is
not started or is aborted.
CV2LimitsInv and CVManLimiting are True at start
of CV2 - PV2 Autotuning or during CV2 - PV2
Autotuning. When True, CV2 - PV2 Autotuning is
not started or is aborted.
CV3LimitsInv and CVManLimiting are True at start
of CV3 - PV2 Autotuning or during CV3 - PV2
Autotuning. When True, CV3 - PV2 Autotuning is
not started or is aborted.
CV1Initializing is True at start of CV1 - PV2
Autotuning or during CV1 - PV2 Autotuning. When
True, CV1 - PV2 Autotuning is not started or is
aborted.
CV2Initializing is True at start of CV2 - PV2
Autotuning or during CV2 - PV2 Autotuning. When
True, CV2 - PV2 Autotuning is not started or is
aborted.
CV3Initializing is True at start of CV3 - PV2
Autotuning or during CV3 - PV2 Autotuning. When
True, CV3 - PV2 Autotuning is not started or is
aborted.
CV1EUSpan or PV2EUSpan changes during CV1 -
PV2 Autotuning. When True, CV1 - PV2 Autotuning
is aborted.
CV2EUSpan or PV2EUSpan changes during CV2 -
PV2 Autotuning. When True, CV2 - PV2 Autotuning
is aborted.
CV3EUSpan or PV2EUSpan changes during CV2 -
PV3 Autotuning. When True, CV3 - PV2 Autotuning
is aborted.
Values
Bit 3 of AtuneCV2PV2Status
Bit 3 of AtuneCV3PV2Status
Bit 4 of AtuneCV1PV2Status
Bit 4 of AtuneCV2PV2Status
Bit 4 of AtuneC3PV2Status
Bit 5 of AtuneCV1PV2Status
Bit 5 of AtuneCV2PV2Status
Bit 5 of AtuneCV3PV2Status
Bit 6 of AtuneCV1PV2Status
Bit 6 of AtuneCV2PV2Status
Bit 6 of AtuneCV3PV2Status
Bit 7 of AtuneCV1PV2Status
Bit 7 of AtuneCV2PV2Status
Bit 7 of AtuneCV3PV2Status

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents