Process Control Instructions
CV1HandFB
REAL
CV2HandFB
REAL
CV3HandFB
REAL
CV1HandFBFault
BOOL
CV2HandFBFault
BOOL
CV3HANDFBFault
BOOL
CV1Target
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
CV1 HandFeedback value. CV1 set to
this value when in Hand mode and
CV1HandFBFault is FALSE (good
health). This value would typically
come from the output of a field
mounted hand/auto station and
would be used to generate a bumpless
transfer out of Hand mode. If value of
CV1HandFB < 0 or > 100, set unique
Status bit and limit value used for CV1.
CV2 HandFeedback value. CV2 set to
this value when in Hand mode and
CV2HandFBFault is FALSE (good
health). This value would typically
come from the output of a field
mounted hand/auto station and
would be used to generate a bumpless
transfer out of Hand mode. If value of
CV2HandFB < 0 or > 100, set unique
Status bit and limit value used for CV2.
CV3 HandFeedback value. CV3 set to
this value when in Hand mode and
CV3HandFBFault is FALSE (good
health). This value would typically
come from the output of a field
mounted hand/auto station and
would be used to generate a bumpless
transfer out of Hand mode. If value of
CV3HandFB < 0 or > 100, set unique
Status bit and limit value used for CV3.
CV1HandFB value bad health
indicator. If the CV1HandFB value is
read from an analog input, then
CV1HandFBFault will normally be
controlled by the status of the analog
input channel. If CV1HandFBFault is
TRUE, it indicates an error on the input
module, set bit in Status.
CV2HandFB value bad health
indicator. If the CV2HandFB value is
read from an analog input, then
CV2HandFBFault will normally be
controlled by the status of the analog
input channel. If CV2HandFBFault is
TRUE, it indicates an error on the input
module, set bit in Status.
CV3HandFB value bad health
indicator. If the CV3HandFB value is
read from an analog input, then
CV3HandFBFault will normally be
controlled by the status of the analog
input channel. If CV3HandFBFault is
TRUE, it indicates an error on the input
module, set bit in Status.
Target value for CV1.
Chapter 1
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0
FALSE = Good Health
Default = FALSE
FALSE = Good Health
Default = FALSE
FALSE = Good Health
Default = FALSE
Valid = 0.0...100.0
Default = 0.0
157